Active Power Filter (APF)
Active Power Filter (APF)
The SinPOWER brand active power filter by ACTIONPOWER is a single-module high-capacity active power filter designed based on site load characteristics, with module capacities covering 10A (iBook SiC technology), 10A~40A (high precision), 50A, 75A, 100A, 150A, 200A, etc. The capacity of a single cabinet can reach up to 1500A. Its application fields include various industrial power distribution sites such as equipment manufacturing, petrochemical industry, metallurgy, textile industry, building materials industry, light industry, etc.; civil architecture industries like large data centers, hospitals, airports, large venues, and high-end buildings; and urban/rural smart grids, the semiconductor industry, photovoltaic industry, urban rail transit industry, among others. The high-precision products are mainly used in special industries such as industrial air conditioning.
Parameter
  • Input voltage380V,-30%~+20%;208V,-10%~+20%
  • Input frequency50Hz,±10%
  • Connection mode3P3W/3P4W (compatible with both)
  • Module capacity10A、20A、30A、40A、50A、75A、100A、150A、200A
  • Single cabinet capacity50A~1500A
  • Response time≤5ms
  • Power loss<3%
  • Harmonic compensation times2 to 61 times
  • Compensation rateNot less than 95%
  • Compensation functionHarmonics, three-phase imbalance, reactive power, priority selectable.
  • Compensation modeHarmonic full compensation, harmonic and imbalance, specific order compensation, harmonic source/reactive power source.
  • CT scan requirements5A, sampling available on both the grid side and the load side.
  • ProtectionMultiple protection functions such as overcurrent, overheating, over and under voltage protection.
  • IP gradeModule: IP20, complete machine: IP30; higher IP grades for the complete machine can be customized
  • Ambient temperatureWorking temperature: -10°C ~ 50°C (derating above 40°C)Storage temperature: -25°C ~70℃
  • Ambient humidity≤95% (45°C) no condensation
  • Altitude<2000m; for altitudes over 2000 meters, use according to derating requirements specified in GB/T3859.2
  • Incoming modeWhole cabinet: Top entry line/bottom entry line/through-busbar on top of the cabinet
  • Overall dimensions10A(ibook):243mm×167mm×88mm(2U);10A~40A (High precision): 380mm x 400mm x 88mm (2U);50A/75A:440mm×560mm×88mm(2U);100A/150A:440mm×560mm×145mm(3.3U);200A:440mm×560mm×228mm(5.2U);Complete machine: 800 x 1000 x 2200; dimensions of the complete machine can be
  • Installation methodModule: rack-mounted or wall-mounted; complete machine: freestanding installation
  • Display screen7-inch touch screen
  • Display contentVoltage, load current, compensating current, grid-side current, voltage distortion rate, current distortion rate
  • Communication interface and communication modeRS485, LAN, WiFi (optional configuration)
  • Communication protocolModbus Protocol
  • Model