Technical Parameters 1
Input voltage380V,-30%~+20%
Input voltage208V,-10%~+20%
Input frequency50Hz,±10%
Connection mode3P3W/3P4W (compatible with both)
Module capacity30kvar、50kvar、100kvar、150kvar 25kvar、50kvar
Single cabinet capacity30kvar~1000kvar 25kvar~500kvar
Response time≤5ms
Power loss<3%
Control modeReactive power compensation, constant reactive power, constant power factor.
Control accuracyNot less than 2.5%
Compensation functionReactive power, three-phase imbalance; priority selectable and settable
CT scan requirements5A, sampling available on both the grid side and the load side.
ProtectionMultiple protection functions such as overcurrent, overheating, over and under voltage protection.
IP gradeModule: IP20, complete machine: IP30; higher IP grades for the complete machine can be customized.
Ambient temperatureWorking temperature: -10°C ~ 50°C (derating above 40°C);Storage temperature: -25°C ~70℃
Ambient humidity≤95% (45°C), no condensation
Altitude<2000m; for altitudes over 2000 meters, use according to derating requirements specified in GB/T3859.2
Incoming modeWhole cabinet: Top entry line/bottom entry line/through-busbar on top of the cabinet
Overall dimensions(W×D×H: mm)Module::50kvar:440mm×560mm×88mm(2U);100kvar:440mm×560mm×145mm(3.3U);150kvar:440mm×560mm×228mm(5.2U)。Complete machine: 800 x 1000 x 2200; dimensions of the complete machine can be customized
Installation methodModule: rack-mounted or wall-mounted; complete machine: freestanding installation
Display screen7-inch touch screen
Display contentVoltage, load current, compensating current, grid-side current, voltage distortion rate, current distortion rate
Communication interface and communication modeRS485, LAN, WiFi (optional configuration)
Communication protocolModbus Protocol
Technical Parameters 2
Input voltage690V,±10%
Input frequency50Hz,±5%
Connection mode3P3W
Module capacity150kvar、175kvar、200kvar
Single cabinet capacity150kvar~800kvar
Response time≤10ms
Power loss<3%
Compensation functionInductive reactive power, capacitive reactive power
CT scan requirements5A, sampling available on both the grid side and the load side
ProtectionMultiple protection functions such as overcurrent, overheating, over and under voltage protection.
IP gradeComplete machine: IP20; higher IP grades for the complete machine can be customized.
Ambient temperatureWorking temperature: -10℃~ 50℃ (derating above 40°C);Storage temperature: -25°C ~70℃
Ambient humidity≤95% (45°C), no condensation
Altitude<1000m; for altitudes over 1000 meters, use according to derating requirements specified in GB/T3859.2
Incoming modeWhole cabinet: Top entry line/bottom entry line/through-busbar on top of the cabinet
Overall dimensions(W×D×H: mm)Complete machine: 1400×1000×2200; dimensions of the complete machine can be customized
Display screen7-inch touch screen
Display contentCurrent, voltage, power, distortion rate, etc.
Communication interface and communication modeRS485
Communication protocolModbus Protocol